PCS

PCS (2,217 kVA)

Nidec Industrial Solutions · Water cooled · Central PCS, 1500V

2,217 kVA power conversion system rated at 1500V DC (2000V-ready) with 98.7% peak efficiency and water cooling. Designed for utility-scale BESS with busbar connections on both AC and DC sides, grid forming and black start capability, and IP55 outdoor enclosure with optional IP65 upgrade.

2,217 kVA
Power Rating
98.7%
Max Efficiency
1,500V
Max DC Voltage
IP55
IP Rating
Download Datasheet (PDF)

Specifications

DC Side
Max DC Voltage 1,500V (2,000V-ready)
Min DC Voltage 463V
Max DC Current 2 x 2,450A or 4,900A
DC Ports 1 or 2
Number of DC Inputs Up to 30 + 30 fuses
Connection Type Busbar
AC Side
Rated AC Power 2,217 kVA @ 1500 VDC, 40°C
AC Current 4,000A @ 1500 VDC, 40°C
Rated AC Voltage 320V
AC Voltage Range ±15%
AC Frequency 50 / 60 Hz ±6%
Power Factor 0 (under-excited) to 1 to 0 (over-excited)
THDi @ Pnom < 1%
Connection Type Busbar
Efficiency
Max Efficiency 98.7%
Stand-by Consumption < 250W
Protections
DC Surge Protection Type I+II
AC Surge Protection Class I
AUX Surge Protection Class II
Insulation Monitoring Ground fault monitoring with digital signals
General
Dimensions (W x D x H) 2,000 x 2,000 x 2,730 mm
Weight 4,500 kg
Cooling Air cooled / Water cooled
IP Rating IP55 (IP65 optional)
Operating Temperature −20°C to +40°C (−40°C optional, 10% derating at 50°C)
Max Altitude 1,000 m without derating / 4,000 m with derating
Sound Pressure @ 10m < 60 dB(A)
Corrosion Protection C4H (C5H optional)
Communication Modbus TCP/IP (Profinet optional)

Key Features

  • 2000V DC-ready architecture supporting next-generation high-voltage battery strings
  • 98.7% peak efficiency with water-cooled thermal management
  • Grid forming and black start capability for islanded or weak-grid operation
  • Full four-quadrant reactive power support across the entire power factor range
  • Dual DC port configuration with up to 60 fused string inputs
  • Ultra-low harmonic distortion (THDi < 1%) at nominal power
  • IP55 outdoor enclosure with optional IP65 and C5H corrosion upgrades
Product Certifications
IEC 62477-1 IEC 62109-1 IEC 62109-2 IEC 62909-1 IEC 62909-2 UL 1741 IEC 62920
Environmental Compliance
CE UKCA
About the Manufacturer
Nidec Industrial Solutions
Roche-la-Molière, France · Founded 1973

Nidec Industrial Solutions operates through its Nidec Conversion division, with manufacturing in France, Italy, USA and China. The company inherited over a century of power electronics expertise when Nidec acquired Ansaldo Sistemi Industriali in 2013. Nidec supplies power conv...

View full Nidec Industrial Solutions profile →
PCS (2,217 kVA) Datasheet
Nidec Industrial Solutions · PDF
Download Datasheet
or
Get notified when Nidec Industrial Solutions releases new products
We track spec changes so you don't have to.